Pepperl+Fuchs KCD2-SR-Ex2 Switch Amplifier
This Pepperl+Fuchs KCD2-SR-Ex2 Switch Amplifier / Isolated Barrier is used for intrinsic safety applications. The device transfers digital signals from NAMUR sensors or dry contacts from the hazardous area to the non-hazardous area.
Features:
- 2-channel isolated barrier
- 24 V DC supply (Power Rail)
- Dry contact or NAMUR inputs
- Relay contact output
- Line fault detection (LFD)
- Housing width 12.5 mm
- Up to SIL2 acc. to IEC 61508
The proximity sensor or the mechanical contact controls the control side load for a relay contact output. The device output changes the state when the input signal changes the state. Via switches the mode of operation can be reversed and the line fault detection can be switched off. During a fault condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44. If the device is operated via Power Rail, additionally a collective error message is available. Due to its compact housing design and low heat dissipation, this device is useful for detecting positions, end stops, and switching states in space-critical applications.
KCD2-SR-Ex2 Specifications:
Depth | 114mm |
---|---|
ETIM Class | NAMUR switching amplifier |
ETIM Group | Sensors |
Height | 119mm |
Number of Channels | 2 |
Number of Inputs, according to NAMUR | 1 |
Number of Inputs, Potential-Free | 1 |
Rated Supply Voltage at AC | 19 – 30V |
SIL according to IEC 61508 | 2 |
Type of Electric Connection | Screw connection |
Type of Power Supply | Active |
Width | 12.5mm |
Alternative Part Number | 70112153 |
Tariff Code | 85044082 |
Generic Code | PFPA30 |
Approved for | Ex ia] IIC , [Ex ia] I |